How to read a tank dip chart, step by step
A dip chart (calibration chart) lists how many litres a particular tank holds at each dip height. Measure the dip with the dip rod, find the two rows on either side of your reading, and add the share of the difference between them for the extra millimetres.
By the adiPower team, Adimyra Systems · Published 5 November 2026 · Facts checked 5 November 2026
Taking the dip
- Stop sales from the tank's nozzles and let the fuel settle for a few minutes.
- Lower the clean dip rod straight down until it touches the bottom.
- Read the wet mark at eye level, in centimetres and millimetres.
- Check for water with water-finding paste on the rod's tip and note the water dip.
- Take a second dip; the two should agree.
Reading between two rows
| Dip (cm) | Litres |
|---|---|
| 152 | 12,340 |
| 153 | 12,420 |
For a dip of 152.4 cm: the difference between the rows is 80 litres per cm, so 0.4 cm adds 0.4 × 80 = 32 litres. Stock is 12,340 + 32 = 12,372 litres. Take off the litres for any water dip from the same chart.
Use the chart made for that tank. Two tanks of the same size can have different charts.
Read next
Run tonight's shift on adiPower
Set up tanks, nozzles and today's rates in the trial, or open the demo first.